Products
 
 
MULTI CORE INSTRUMENTATION & CONTROL CABLES
 
‘Udey’ Instrumentation & control cables are made as per customer requirements based on various parameters, with the choice of multipair construction, pair identification & proper shield to avoid electrical interface disturbances.
 
CONDUCTOR CHART
 
Cable Conductor type Wire Plating No of Cores
PTFE Stranded / Solid Silver / Nickel plated copper wire 1 to 56
Silicone Bunched / Solid Tinned copper wire 1 to 56
Fibre glass Bunched / Solid Bare / Tinned copper wire 1 to 56
XLPE Bunched / Solid Tinned copper wire 1 to 56
 
Standard Characteristics of Instrumentation Cables
 
Test 0.5 0.75 1.0 1.5 2.5
Sq.mm Sq.mm Sq.mm Sq.mm Sq.mm
 Mutual capacitance core to core(max).pF / metre  <
250 250 250 250 250
 L / R  ratio (max).                                      µH/Ω    <
25 25 40 40 40
 Conductor resistance  @ 20°C.                   Ω / kM   <
39.7 26.5 12.1 12.3 7.41
 Insulation resistance                                 Meg Ω / kM  >
100 100 100 100 100
 Core  to core / screen / armour -
         
 Resistance for 1 hour @ 20°C.                   Meg Ω / kM  >
10 10 10 10 10
 Screen to screen resistance -
         
 1 hour @10°C.                                         Meg Ω /1 kM >
1 1 1 1 1
  
MULTIPAIR THERMOCOUPLE EXTENSION / COMPENSATING CABLES
 
A Thermocouple measuring point is formed by joining two dissimilar metals as one circuit, which when exposed to different temperatures generates a net thermal electromotive force ( E.M.F.) Each thermocouple cable has two cores of such dissimilar conductors forming a pair and for multiple measuring points multi pair cable is used.

‘Udey’ offers the complete range of cables suited for High Volt & Temperature application with various combinations of different conductors, insulations and shields as as per customer application & requirement.

 
INSULATION CHART
 
Material
Operating temp
Dielectric Strength
P.T.F.E
260°C
>10 kV
Silicone Rubber
180°C
>5kV
Fibre Glass Braid
250°C
 >2.5kV
XLPE
135°C
>5kV
PVC (HR/FRLS)
105°C